ABB FEP631 DN50 ProcessMaster Electromagnetic Flowmeter for Conductive-Liquid Measurement
ABB ProcessMaster FEP631 DN50 Electromagnetic Flowmeter Configuration
ABB model FEP631.F1.D2.0050.A1.T1.C.1.D.0.A.70.E.2.G0.A-CRP-RCD-TV2 is a configured ProcessMaster FEP630-series electromagnetic flowmeter. The “0050” portion identifies a DN50 configuration, while the remaining characters define the process connection, liner, electrodes, transmitter, power, communication, approvals and accessories.

| ProcessMaster data | Family specification / configuration note |
|---|---|
| Requested model | FEP631.F1.D2.0050.A1.T1.C.1.D.0.A.70.E.2.G0.A-CRP-RCD-TV2 |
| Nominal size | DN50 according to the supplied order code |
| Measurement | Volumetric flow of electrically conductive liquids |
| Published accuracy | Standard 0.4% of rate; family options may provide 0.3% or 0.2% |
| Protection | IP67 or IP68 depending on the ordered sensor and transmitter arrangement |
| Diagnostics | Empty pipe, partial filling, gas bubbles, electrode impedance, conductivity and sensor temperature at family level |
Application checks
The pipe must remain full and the liquid must meet the minimum conductivity requirement. Confirm normal and maximum flow, pressure, temperature, flange rating, liner and electrode compatibility, grounding method, upstream disturbances and whether an integral or remote transmitter is required. Non-conductive hydrocarbons, gases and steam are not suitable for electromagnetic measurement.
During commissioning, verify flow direction, pipe grounding, engineering units, configured range and zero-flow condition. The image is reused from the existing FEP631 product family and is not uploaded again. Final supply must match the complete order code, nameplate and current ABB configuration documents.